MSA Ultima X5000 – Gas Monitor / 1 Sensor with Relay
The MSA Ultima X5000 is the future of Gas Detection for oxygen, toxic, and combustible gases. With a newly advanced OLED Display capable of 9 languages, it is easy to read and navigate due to the industry-first touch screen interface, allowing for a tool free user experience. MSA’s patented XCell sensors with TruCal increase calibration cycles for as long as 18 months (H2S & CO specific). The Ultima X5000 supports up to 2 Digital sensors or 1 IR detector and 1 digital sensor simultaneously with 4 wire connections (Configurable with 1 or 2 sensors).
MSA’s patented TruCal Technology in the Ultima X5000 self-checks 4x every day resulting in stress free operation, better stability and extended calibration cycles. TruCal compensates for factors that may cause electrochemical sensor drift by continually monitoring sensor integrity and compensating for factors that may impact this (H2S & CO TruCal sensors only), truly separating itself from competition.
An acoustic signal is sent every 6 hours ensuring the sensor inlets are not blocked, allowing gas to reach the sensor, known as diffusion supervision. If blocked the unit will go into fault mode, then return to normal operation once the blockage is removed. Sensors can be selected without Diffusion Supervision
SafeSwap ensures the gas sensors can be replaced quickly and safely without turning off the device. Sensors can be mixed and matched to meet your gas detection needs, further displaying the unique benefits of this product. This device is fully configurable allowing it to be tailored to your specific needs and can be used across a variety of applications. Get in touch with our sales team to build your own configuration.
- Bright green, yellow and red status LEDs for extreme visibility
- Real time data in your hand via Bluetooth wireless technology
- Reduce time of setting up by at least 50% through the X/S connect app
- Check status and receive alerts up to 75ft (23m) away
- Adjust settings/alarms/setpoints
- Fits existing MSA X series wall mounts
- Sensor readings adjusted in line with environmental factors
- 3-year warranty & expected life of around 5-years for XCell sensors
- Corrosion resistant 316L stainless steel
- IP66 Rated
Combustible Gas Sensor Type |
| ||
Toxic Gas & Oxygen Sensor Type |
| ||
Sensor Measuring Ranges |
| ||
Typical Sensor Life | 5 years – XCell Sensors 10 years – infrared | ||
Sensor Performance | T90 (Typical) | Repeatability | Zero Drift (Per Year) |
XIR Plus Comb | < 2 sec. | < +/- 1% LEL | n/a |
XIR Plus CO2 | < 6 sec. | < +/- 1% Vol | n/a |
XCell Comb | < 22 sec. | < +/- 3% LEL | ≤ 5% LEL |
XCell CO | < 9 sec. | < +/- 1% | ≤ 1% full scale |
XCell H2S | < 23 sec. | < +/- 1% | ≤ 1% full scale |
XCell O2 | < 11 sec. | < +/- 0.1% Vol | ≤ 0.2% Vol |
XCell SO2 | < 6 sec. | +/- 1% | ≤ 1%FS per mo. |
Approvals Classification | Divisions (US/Canada) Class I, II, III; Div 1&2, T4/T5/T6; Zones (Global) Ex db nA IIC T5 Gb (Class I, Zone 1/ Zone 2) Ex tb IIIC T85°C Db (Class II, Zone21) Enclosure rating Type 4X, IP66 Markings vary by component. See Manual for specific component markings. | ||
Warranty |
| ||
Approvals | CSA, ATEX, IECEx, Inmetro, DNV Marine, CE Marking. Complies with C22.2 No. 152, FM 6320 RED, FCC, Suitable for SIL 2 | ||
Operating Temperature Range | XCell: -40°C to +60°C XIR PLUS: -40°C to +60°C (may differ by gas, see manual) | ||
Storage Temperature Range | 40°C to +60°C | ||
Relative Humidity (non-condensing) |
| ||
Input Power | 11 to 30 VDC, 3 wire, <5W nominal | ||
Signal Output | Dual 4-20 mA current source, HART | ||
Bluetooth (optional) | Bluetooth Low Energy (BLE) v4.3 or higher | ||
Relay Ratings |
| ||
Relay Modes | Common, discrete, horn | ||
Nominal max Power (w/ relays) |
| ||
EMC Directive | Complies with EN 50270, EN 61000-6-4, EN 61000-6-3 | ||
Display | Organic LED (multi-lingual) with Contrast Ratio of 2000:1 and View Angle of 160° | ||
Hart | HART 7, HART device description language available | ||
Faults Monitored | Low supply voltage, RAM checksum error, flash checksum error, EEPROM error, internal circuit error, relay, invalid sensor configuration, sensor faults, calibration faults, general system) | ||
Wiring Requirements | 3-wire (single sensor) or 4-wire (dual sensor) shielded cable. Refer to manual for mounting distances and wire gauge. | ||
HOUSING (W X H) w/ XCell Sensor w/ XCell Sensor & XIR Sensor | 5.88” x 5.71” [150 mm x 145mm] 5.88” x 10.15” [150 mm x 258 mm] 13.42” x 10.15” [341 mm x 258 mm] | ||
Lid (Depth) w/ Relay Board w/o Relay board |
| ||
Weight | 8.8 lbs (4 kg) – 316 SS |